A 138 kV substation, unused.
Available now.

Power transformers and circuit breakers from a single cancelled capital project, engineered as one 138 kV set, factory new, never energized. Complete with certified factory test reports and released manufacturer drawings. Available as individual units or by the lot.

Disclosed up front: the transformers are DETC, not LTC. They suit designs where voltage regulation is handled elsewhere. At 137,920 lb each they are a permitted heavy-haul move.

Power transformer, HV-side elevation
LOT A · HV-SIDE ELEVATION · MAVERICK OUTLINE
Power transformers
7
Aggregate, 7 × 50 MVA at 55°C
350 MVA
New-build lead time at this class
40-70 wk
These units
On the ground
Lot A7 AVAILABLEConfirmed Nov 19, 2026

Power transformers

Seven 138 kV substation transformers, new and unused, never energized. 30 / 39.9 / 50 MVA ONAN/ONAF/ONAF at 55°C rise, 33.6 / 44.7 / 56 MVA at 65°C. HV 138,000 V delta, 650 kV BIL. LV 13,800Y / 7,967 V, 110 kV BIL. Three phase, 60 Hz, Dyn1, copper HV and LV windings, five-position DETC. Built February 2025 to IEEE C57.12.00, with a certified factory routine test report.

Engineering note · impedance base

Impedance is quoted on both bases. A fault study run against the 56 MVA rating uses 17.29 %, not the 9.26 % figure carried on the 30 MVA base.

Power transformer, HV-side elevation
HV-SIDE ELEVATION · DRAWN FROM RELEASED DIMENSIONAL DATA

Ratings

RatingValue
Capacity, 55°C rise30 / 39.9 / 50 MVA
Capacity, 65°C rise33.6 / 44.7 / 56 MVA
CoolingONAN / ONAF / ONAF
Phase / frequency3 Ø · 60 Hz
HV winding138,000 V delta
LV winding13,800Y / 7,967 V
Rated current, HV / LV125.5 A / 1,255.1 A
Vector groupDyn1
BIL, HV / LV650 kV / 110 kV
Impedance, 30 MVA base9.26 % at rated tap
Impedance, 56 MVA base17.29 % at rated tap
Zero-sequence impedance10.30 % (0.65 Ω/phase)
StandardIEEE C57.12.00
Date of manufactureFebruary 2025

Tap changer

TapHV voltsA @ 56 MVALink
A144,900223.14-5
B141,450228.65-3
C138,000234.33-6
D134,550240.36-2
E131,100246.62-7

Five position, de-energized operation only.

Construction

ItemDetail
CoreStacked
WindingsCopper, HV and LV
Insulating fluidType II mineral oil, specified under 2 PPM PCB
Oil volume5,490 gal: 4,890 tank / 600 radiator
Cooling fans12
Local control panelNEMA 3R
PaintANSI 61 light gray
Protection and monitoringSudden pressure relay, pressure relief device, oil and winding temperature indicators, oil level indicator, N2 gas equipment
TankWelded, full vacuum and 14.7 psi internal

Bushing CTs

CTLocationRatioClass
CT01-03H1, H2, H3600:5 MRC800
CT04-06X1, X2, X32000:5 MRC800
CT07X2 (WTI)3500:5 SR3.2 CL
CT08X02000:5 MRC800

Weights

ItemValue
Core and coil67,615 lb
Tank and fittings30,460 lb
Insulating oil39,845 lb
Shipping weight84,100 lb
Total weight137,920 lb
Overall L × W × H205 × 196 × 201 in
Shipping L × W × H192 × 96 × 144.5 in

Routine tests

Routine test · documented unitGuaranteeMeasured
Turns ratio error across taps±0.5 %0.02-0.25 %
Polarity and phase relationshipDyn1Dyn1
Winding resistance @75°C, HV—1.5172-1.5187 Ω
Winding resistance @75°C, LV—0.01050-0.01054 Ω
Insulation resistance, HV-LV—19,400 MΩ
Insulation resistance, HV-earth—20,800 MΩ
Insulation resistance, LV-earth—15,900 MΩ
Core-clamp insulation—8,130 MΩ
Insulation power factor @20°C0.5 %0.19-0.22 %
No-load loss @100 % / @110 %—22,601 / 27,459 W
Exciting current @100 % / @110 %—0.16 % / 0.25 %
Efficiency @PF 1.0, 100 % / 50 %—99.66 / 99.72 %
Applied voltage, HV-earth207 kVWithstood
Applied voltage, LV and neutral-earth34 kVWithstood
Induced overvoltage, LV Ø-Ø @180 Hz27.60 kVWithstood
Oil leakage, +0.50 kgf/cm² × 12 h—Passed
Control cubicle dielectric and wiring—Passed
Operation test, all devices—Passed
Bushing CT ratio, polarity, IR—Passed, >100 MΩ
Sweep frequency response analysis—Recorded

Performed on the documented unit, February 2025.

Losses by tap

Losses and impedanceTap ATap CTap E
Load loss @75°C, 30 MVA (W)76,32677,89680,957
Total loss @75°C, 30 MVA (W)98,927100,497103,558
Load loss @85°C, 56 MVA (W)270,714276,387287,130
Total loss @85°C, 56 MVA (W)293,315298,988309,730
Impedance @75°C, 30 MVA (%)9.229.269.42
Impedance @85°C, 56 MVA (%)17.2017.2917.59

Type tests

Type test · sister unitGuaranteeResult
Lightning impulse, HV winding650 kVWithstood
Chopped wave, HV winding715 kVWithstood
Lightning impulse, LV and neutral110 kVWithstood
Top oil temperature rise, ONAN55 K42.6 K
Avg winding rise, HV / LV55 K43.5 / 42.4 K
Hot-spot rise, HV / LV—54.6 / 53.2 K
Sound level, no cooling75 dB71.5 dB

Type tests were performed on a sister unit of the same design in December 2024, standard practice for a production run. Results are not attributed to an individual unit.

Lot B5 AVAILABLEConfirmed Nov 19, 2026

145 kV SF6 circuit breakers

Five SF6 dead tank circuit breakers, new and unused. 145 kV / 2000 A / 40 kA, 650 kV BIL, 60 Hz. Rated interrupting time 3.0 cycles. Spring mechanism with 125 VDC control and dual trip coils. Twelve 1200:5 multi-ratio C800 bushing CTs. IEEE 693 seismic qualified to 0.2 g RRS. US built, 5,555 lb each.

Dead tank breaker elevation
DEAD TANK ELEVATION · REPRESENTATIVE ARRANGEMENT
Ratings
TypeSF6 dead tank
Rated maximum voltage145 kV
Rated interrupting time3.0 cycles
Voltage range factor K1.0
Short circuit, terminal fault40 kA
90 % short line fault40 kA
Short circuit withstand3 s
DC component55.2 %
Continuous current2000 A
Frequency60 Hz
Full wave impulse withstand650 kV
Duty cycleO-0.3s-CO-15s-CO
Out-of-phase switching10 kA
Temperature range−30°C to +40°C
Capacitance switching, voltage factor1.4
Line charging / isolated bank / back-to-back160 / 400 / 400 A
Inrush peak / frequency20 kA / 4,250 Hz
Construction and control
MechanismSpring
Closing coil125 VDC, 3.5 A
Trip coils125 VDC, 3.5 A each, dual
Spring charge motor125 VDC, 1.6 kW
Space heater120 VAC, 190 W
Bushing CTsTwelve, 1200:5 MR, C800, RF 2.0
BCT taps100:5 through 1200:5
BushingsPorcelain, ANSI 70 gray, 92 in creepage, 44.5 in strike
Control cabinetNEMA 3R steel
SF6 pressure @20°C93 / 78 / 74 psig: normal / alarm / lockout
SF6 weight71 lb
Seismic0.2 g RRS per IEEE 693
Weight, breaker / BCTs / gas3,744 / 1,740 / 71 lb
Total weight5,555 lb
Shipping L × W135.8 × 85.1 in
OriginDesigned and manufactured in the USA
Condition, documents, freight

New, unused, never energized

Both lots, released from a cancelled capital project. On the transformers: factory paint intact with no field weathering, bushings not yet mounted with openings sealed and wrapped from the factory, stored outdoors on timber cribbing.

Documentation
DocumentStatus
Certified factory routine test reportAvailable now
Type test results, sister unitAvailable now
Outline, nameplate and layout drawingsAvailable now
Instruction and maintenance manualAvailable now
Breaker outline and schematic drawingsAvailable now
Oil test report and PCB certificateIn process
Manufacturer identity, serials, locationNDA / LOI
Freight · transformers
Shipping weight per unit84,100 lb
Total weight per unit137,920 lb
Shipping envelope192 × 96 × 144.5 in
Move classificationPermitted heavy haul
Rigging, permits, escortsBuyer's account

At 137,920 lb per unit this is a permitted heavy-haul move in every jurisdiction. Freight is the largest single variable in landed cost at this class. A route survey is recommended before an offer is firmed.

Terms

How a sale closes

Pricing is released by reply to a qualified request. Offers considered.

Seller of recordMaverick Wholesale LLC
PricingUSD, EXW storage location, released by reply
Freight, rigging, permitsBuyer's account unless quoted separately
ClosingIndependent escrow: buyer funds escrow, title transfers and funds release at the same closing
InspectionAvailable to a qualified buyer by appointment
StructureIndividual units or by the lot
Request the technical package

When do you need to energize?

Tell us about the 138 kV service and the date it has to be live. We reply with pricing, drawings and test reports.

Call or text · 689-666-0287
Source protection

Manufacturer identification, serial numbers, order and drawing numbers, unit tags and storage location are withheld at this stage. Brand and general location are released under executed NDA; serial numbers are released at LOI.

Availability

Pricing is offered subject to prior sale and to material remaining available at time of order. This document is an offering, not a binding commitment to sell.

Data and warranty

Impedance, loss and dielectric values are transcribed from the certified factory routine test report; type test results are from a sister unit of the same design. Oil is specified under 2 PPM PCB per the released manufacturer drawing; oil analysis furnished on request. Material offered as-is, where-is with no warranty expressed or implied unless stated in a signed purchase agreement. Manufacturer warranty status has not been established. Buyer is responsible for verifying suitability for the intended application. Complete documentation furnished on execution of a confidentiality agreement.