Home / Products / 38 kV fused switchgearMedium voltage · 38 kV
38 kV metal-enclosed fused load-interrupter switchgear
Outdoor lineups of load-break switches and power fuses for 34.5 kV systems. The shortest lead time in our 38 kV range: 8 to 10 weeks from the later of purchase order or approved drawings.
- Rated maximum voltage
- 38 kV
- Main bus
- 600 A
- Short-circuit
- 25 kA
- Lead time
- 8-10 wk
| Rated maximum voltage | 38 kV (34.5 kV system) |
| System | 3-phase, 3-wire, 60 Hz |
| Main bus | 600 A copper, silver-plated |
| Short-circuit | 25 kA momentary and 2 s |
| BIL | 150 kV |
| Enclosure | NEMA 3R outdoor, ANSI 61 light gray |
| Cable entry | Bottom |
| Access | Front and rear |
| Space heaters | Included |
| Standards | Designed per IEEE C37.20.2, C37.20.3 and C37.20.4. Not UL listed. |
| Lead time | 8 to 10 weeks from the later of purchase order or approved drawings |
| Load-break switches | 1000 A continuous, 25 kA 2 s, manual quick-make / quick-break, fault-close rated |
| Fuses | Boric-acid, refillable |
| 600 A-class feeders | 300E fuses, two per phase in parallel |
| Smaller feeders | 50E fuses |
| Spare fuses | One spare set per rating included |
| Section | Width | Contents |
|---|---|---|
| Main, non-fused | 60 in | CTs, ammeter with selector switch |
| Bus transition | 30 in | Bus only |
| Fused feeder | 60 in | Load-break switch and fuses |
Section depth and height: 87 in D × 128 in H.
| Lineup | Main, bus transition and four fused feeders |
| Overall L × H × D | 330-1/2 × 134 × 86-5/8 in |
| Total weight | About 28,500 lb |
| Per switch section | About 5,000 lb |
| Per transition section | About 3,500 lb |
Where it fits
Where the single line calls for breakers and relaying, we will say so. Where fused load-interrupter switches can do the job, this lineup is often the difference between making the energization date and missing it.
Send the single line. We will come back with options and lead times.
Calls and texts are answered around the clock and every request is logged.